PingDo Logo

PingDo.net

by GridFix
View Mode
Back to Toolkit

Low Current Cable Sizing

Professional cable selection for structured cabling & low-voltage systems

5%

Recommended Cable Size

16.0mm²
VOLTAGE DROP
0.57V (2.4%)
POWER LOSS
2.9W
MAX CURRENT (DERATED)
54.4A

Cable Size Comparison

CABLE SIZEMAX CURRENTVOLTAGE DROPDROP %STATUS
16.0mm²54.4A0.57V2.4%✓ OK
6 AWG (13.3mm²)80.8A0.65V2.7%✓ OK
10.0mm²40.0A0.92V3.8%✓ OK
8 AWG (8.37mm²)58.4A1.03V4.3%✓ OK
6.0mm²28.8A1.54V6.4%VOLT DROP
10 AWG (5.26mm²)44.0A1.66V6.9%VOLT DROP
4.0mm²22.4A2.31V9.6%VOLT DROP
12 AWG (3.31mm²)32.8A2.63V11.0%VOLT DROP
2.5mm²16.8A3.71V15.4%VOLT DROP
14 AWG (2.08mm²)25.6A4.18V17.4%VOLT DROP
1.5mm²12.0A6.05V25.2%VOLT DROP
16 AWG (1.31mm²)17.6A6.65V27.7%VOLT DROP
1.0mm²8.0A9.05V37.7%VOLT DROP
18 AWG (0.82mm²)12.8A10.55V44.0%VOLT DROP
0.75mm²4.8A12.25V51.0%OVERCURRENT
20 AWG (0.52mm²)8.8A16.80V70.0%VOLT DROP
0.5mm²2.4A18.00V75.0%OVERCURRENT
22 AWG (0.33mm²)5.6A26.75V111.5%VOLT DROP
Engineering Notes: Voltage drop calculations include loop resistance (supply + return). CCA (Copper Clad Aluminum) has 61% conductivity of pure copper. Installation derating: conduit/tray reduces ampacity by 20%. For critical applications, limit voltage drop to 3% for optimal performance. Always verify with local electrical codes (NEC, IEC, BS 7671).

Low Current Cable Engineering

Structured Cabling Systems

Low-current cabling encompasses all electrical systems operating below 50V AC or 120V DC. This includes fire alarm systems, access control, CCTV surveillance, building automation (BMS), audio/visual systems, and Power over Ethernet (PoE) infrastructure.

Unlike high-voltage power distribution, low-current systems are highly sensitive to voltage drop. A 5% voltage drop in a 24V DC system results in only 22.8V at the load, which can cause equipment malfunction, reduced sensor accuracy, or complete system failure.

Critical Design Considerations

  • Voltage Drop Limits: Industry standard is 3-5% maximum for low-voltage systems
  • Loop Resistance: Always account for both supply and return conductors (2× cable length)
  • CCA vs Copper: Copper Clad Aluminum has only 61% conductivity of pure copper
  • Temperature Derating: Ambient temperature above 30°C requires ampacity reduction
  • Conduit Fill: NEC limits conduit fill to 40% for 3+ conductors
  • Fire Alarm Circuits: NFPA 72 requires dedicated calculations for notification circuits

Common Applications

Fire Alarm Systems (12V/24V DC)

Notification Appliance Circuits (NAC) for strobes and horns. NFPA 72 requires voltage at end-of-line to be within 16-33V for 24V nominal systems. Typical cable: 18 AWG for short runs, 14 AWG for extended circuits.

Access Control & CCTV (12V DC)

Electromagnetic locks draw 500-600mA, card readers 100-200mA. PTZ cameras can draw 2-3A during pan/tilt operations. Use 18 AWG minimum for locks, 16 AWG for PTZ cameras over 30m.

Power over Ethernet (48V DC)

IEEE 802.3af (15.4W), 802.3at (30W), 802.3bt (60-90W). Cat5e/Cat6 uses 24 AWG conductors. Voltage drop critical for PoE+ devices at 100m cable runs. Always use solid copper, never CCA.

Cable Material Comparison

PropertyPure CopperCCA
Conductivity100%61%
Fire ResistanceExcellentPoor
NEC/NFPA CompliantYesLimited
Recommended UseAll applicationsPatch cables only

Technical Standards & References

REF [NFPA-72]
NFPA (2022)
National Fire Alarm and Signaling Code
Voltage drop calculations for fire alarm notification circuits.
VIEW OFFICIAL SOURCE
REF [NEC-725]
NFPA (2023)
National Electrical Code Article 725: Class 1, 2, and 3 Circuits
Requirements for low-voltage remote control, signaling, and power-limited circuits.
REF [TIA-568]
TIA/EIA (2020)
Commercial Building Telecommunications Cabling Standard
Structured cabling standards for data and voice systems.
REF [IEEE-802.3]
IEEE (2018)
Ethernet Standard - Power over Ethernet
PoE voltage drop and power delivery specifications.
Mathematical models derived from standard engineering protocols. Not for human safety critical systems without redundant validation.

Related Engineering Resources

Partner in Accuracy

"You are our partner in accuracy. If you spot a discrepancy in calculations, a technical typo, or have a field insight to share, don't hesitate to reach out. Your expertise helps us maintain the highest standards of reliability."

Contributors are acknowledged in our technical updates.